It is known in electrotechnique that there are fundamentally two types of loadings. Active loadings that generate work and are the resistive loadings. The second type is represented by the reactive loadings; such as inductances and capacitors. From a practical stand-point, in production lines, the biggest part of the loadings is of the inductive type and is represented by electrical motors, transformers, rectifiers etc. The reactive current (inductive in this case) is only meant to create the magnetic field but does not produce work. With a view to energy transmission, this inductive current generates voltage lowerings that are expressed in losses of active power on the lines. The inductive reactive current constitutes a further loading for generators, transformers, transportation and distribution lines. The index that defines the power consumption of magnetic current in delay on the voltage is the power factor cosφ. It is determined by the ratio between active power and apparent power.
CMA 1 SERIES
CMA1 capacitors are used for power factor correction of inductive loadings (transformers, electrical motors, rectifiers) in industrial nets.
With a completely resistive loading, the active power and the apparent power are the same thus the cosφ is 1. Under conditions of inductive loading, the ratio between active power and apparent power will be lower than 1. The lower the cosφ , the higher the absorbed inductive current. Therefore, a plant working with a low cosφ has the following disadvantages: – higher losses of power in transmission in the electrical lines -higher voltage lowerings – higher dimensioning of the generation, transportation, transformation and utilization plants Last but not least, for a low cosφ the companies producing and distributing electrical energy charge – by law- considerable money penalties and sanctions. As a consequence, the energy utilized by the users is lower than that generated by the energy supplier. It is evident that these negative consequences – in a situation of increasing need of energy – are not tolerable in presence of a massive energy saving plan and major performances, both from the point of view of the energy distributor and that of the user. It is therefore important to eliminate or, at least, to reduce the consequences of a low power factor with devices whose behaviour can be compared to a generator of capacitive reactive power as opposed to the phase that is given to the loadings. The capacitors are devices suitable to achieve this purpose.
The single-phase MECO capacitors of the series CMA 1 in metallized polypropylene film are generally created to be assembled with triangle connections for usage in triphase system for power factor correction. The capacitor element is included in an aluminium can which incorporates a pressure sensitive safety device.
Caratteristiche tecniche Technical details | CMA1 - S (Standard Life) | CMA1 - L (Long Life) |
---|---|---|
Tensione nominale (Un) Rated voltage (Un) | 230, 400, 415, 440, 525 | 230, 400, 415, 440 |
Frequenza nominale Rated frequency | 50/60 Hz | 50/60 Hz |
Tolleranza capacità Capacitance tolerance | -5+10% | -5+10% |
Perdite dielettriche Dielectric losses | ≤0,2W/kVar | ≤0,2W/kVar |
Classe di Temperatura Temperature category | -25°C +55°C -25/D | -25°C +55°C - 25/D |
Tensione di prova Test voltage | tra i terminali: 2,15Un/3” verso massa: 3,6kV/10” between terminals: 2,15Un/3” between terminals and case: 3,6kV/10” | tra i terminali: 2,15Un/3” verso massa: 3,6kV/10” between terminals: 2,15Un/3” between terminals and case: 3,6kV/10” |
Terminali Terminals | Faston doppio Double faston | Faston doppio Double faston |
Custodia Case | Alluminio Aluminium | Alluminio Aluminium |
Corrente massima dei terminali Maximum terminal current | 16A | 16A |
Grado di protezione Protection degree | IP00 | IP00 |
Massima corrente d’inserzione Max inrush current | 100 In | 200 In |
Corrente massima di sovraccarico Max overload current | 2 In | 3 In |
Norma di riferimento Reference standard | IEC 60831-1/2; CEI EN 60831-1/2 | |
Aspettativa media di vita Main life expectancy | 140000 h -25/C (+50°C) 120000 h -25/D (+55°C) | 150000 h -25/C (+50°C) 130000 h -25/D (+55°C) |
Resistenza di scarica Discharge resistor | 220kΩ/2W | 220kΩ/2W |
Umidità relativa Relative humidity | <95% | <95% |
Dispositivo di sicurezza Safety device | A sovrapressione Overpressure | |
Altitudine Altitude | ≤2000 mslm masl | ≤2000 mslm masl |